Skip to content
Lumcue
Menu

Interface and scan

Nothing answered on the line

The scan found no lights and no key modules.

Messages this article covers

  • No devices answered. Check the DALI wires and the DALI power, then scan again.
  • Nothing answered on line …
  • The scan found nothing. Check: DALI power supply on, DALI wires connected, interface on the right line, interface plugged in. Then scan again.
  • No light answered on this line. Check the DALI wires and the DALI power, then scan again.

What to check, in order.

  1. The DALI power supply of this line is on.
  2. The drivers have mains power. A driver without mains does not answer on DALI.
  3. The interface is on the right line, and clipped onto the DALI wires.
  4. The DALI wires reach the drivers: no open junction box, no wire left in a terminal block.
  5. Click Scan again.

Lights without an address still count. New drivers without an address show up as lights to address, not as nothing. If the scan finds nothing at all, the line or its power is the problem.

Still stuck?

In the app, open Settings > Diagnostics > Send to Lumcue support and copy the ticket code. Then write to support@lumcue.com with the code, the time, the exact message and what you were doing.