Interface and scan
"No DALI power on the interface"
The interface sees no voltage on the DALI wires.
Messages this article covers
No DALI power on the interface. Check the DALI wires and that the DALI power supply is on.
No DALI power on the interface. Check the DALI wires and that the DALI power supply is on, then scan again.
There is no DALI power
Why it happens. The DALI USB interface reads the line, but it does not power it. The line needs its own DALI power supply, switched on.
What to do.
- Find the DALI power supply of this line and check that it is on (its LED, or its breaker).
- Check that the interface is clipped onto the DALI terminals (DA+ / DA-), not onto mains or another bus.
- Check for a loose or broken DALI wire between the interface and the line.
- Click Scan again.
Still nothing? Measure the line: a powered DALI line reads about 16 V DC between the two DALI wires. If it reads 0 V, the problem is the supply or the wiring, not Lumcue.
Still stuck?
In the app, open Settings > Diagnostics > Send to Lumcue support and copy the ticket code. Then write to support@lumcue.com with the code, the time, the exact message and what you were doing.