Skip to content
Lumcue
Menu

Wall keys

Red bar "Wall keys in a test setting": the buttons do nothing

Wall keys prepared for linking keep a test setting until they are put back.

Messages this article covers

  • Wall keys in a test setting: … Their buttons do not work until they are put back.
  • Connect the DALI interface to put them back.
  • Not put back: … Check the DALI connection and try again. Forget only a key module that was replaced or removed.
  • Key modules … are still in the test setting. Press "Put back" in the red bar first.
  • Nobody watched for 5 minutes, or no button was pressed for 15 minutes, so the wall keys were put back for safety.

Why it happens. To tell look-alike wall keys apart, Lumcue gives them a short test setting. A backup is saved first. Their buttons do not work until they are put back. Normally this happens when you tap Done on the phone.

What to do.

  1. Connect the DALI interface to that installation.
  2. Click Put back in the red bar. Each key module is put back and checked byte for byte, about a minute each.
  3. Wait until the bar disappears before you leave the site.

"Not put back": check the DALI connection and click Put back again. Click Forget only for a key module that was replaced or removed. A forgotten module may keep the test setting; program it or replace it.

Safety timer. If nobody watches for 5 minutes, or no button is pressed for 15 minutes, Lumcue puts the wall keys back by itself.

Contact support before you leave a site with a key module still in the test setting.

Still stuck?

In the app, open Settings > Diagnostics > Send to Lumcue support and copy the ticket code. Then write to support@lumcue.com with the code, the time, the exact message and what you were doing.