DALI Ballast Types: From Fluorescent to LED — What Each Device Type Controls
By Lumcue Team
If you have worked on DALI installations for any length of time, you will have seen datasheets quoting "DT6", "DT8" or "Part 207". These labels describe what a piece of control gear is and which commands it understands. For installers and electrical contractors, knowing the difference matters. It affects addressing, grouping, scene programming and fault-finding.
This article explains how DALI device types work. It covers the main control gear classes, from legacy fluorescent ballasts to modern LED drivers, and shows how that knowledge helps you on site.
What Is a DALI Device Type?
A DALI device type describes a class of control gear, such as a fluorescent ballast or an LED driver. Each class has its own set of type-specific functions and commands on top of the common DALI command set [12]. In practice, a fluorescent ballast and a colour-control LED driver share the basics, such as arc power levels, groups and scenes. Each also responds to extra commands that only make sense for that kind of load.
The Part Number Rule
Device types map directly onto the parts of the IEC 62386 standard. The rule is simple: the DT number is always the IEC 62386 Part number minus 201 [1]. So Part 207 is DT6, and Part 209 is DT8 [1]. Once you remember this, you can move between the two naming systems without a lookup table. If a datasheet says "IEC 62386-207 compliant", you know you are dealing with a DT6 device.
Device Types Apply Only to Control Gear
DT numbers only exist for the control gear Parts (the 2xx series). Input devices and application controllers have none [2]. Your sensors, push-button couplers and controllers are covered by other parts of the standard. They are not described with a DT number. If someone asks for the "device type" of a presence detector, they are mixing up two separate parts of the DALI ecosystem.
How Control Gear Reports Its Device Type
Control gear reports its DT number in reply to the QUERY DEVICE TYPE command. This lets an application controller check the capabilities of the gear on the bus [3]. This is very useful during commissioning. You can confirm that the driver fitted in a luminaire matches what the specification called for, without opening the fitting.
One point often catches people out. A single device can implement several Parts, so it can have more than one DT number [3]. A driver might support the core LED functions and colour control at the same time. When you query such a device, expect it to report more than one type. Do not treat that as a fault.
The Main Device Types in Practice
Below is a walk-through of the device types you are most likely to meet. They run roughly from legacy lamp technologies to current LED equipment.
DT0: Fluorescent Lamp Ballasts (Part 201)
IEC 62386-201 covers control gear for fluorescent lamps, which is device type 0 [6]. This is where DALI started, and many older buildings still have DT0 ballasts in service. When you retrofit or extend these sites, you will often find a mix of legacy fluorescent ballasts and newer LED drivers on the same bus. That works because the core command set is shared. The type-specific features still differ.
DT2: Discharge Lamps / HID (Part 203)
Device type 2, defined in Part 203, covers discharge lamps other than fluorescent lamps. In other words, it covers high-intensity discharge (HID) sources [9]. You are most likely to meet DT2 gear in industrial, warehouse or exterior applications where HID lighting has not yet been replaced.
DT4: Incandescent Supply Voltage Controllers (Part 205)
Device type 4, defined in Part 205, covers supply voltage controllers for incandescent lamps [10]. These are less common on new projects. However, they still appear in heritage buildings, hospitality venues and anywhere tungsten or halogen sources have been kept for their character.
DT5: DC Signal Converters (Part 206)
DT5, defined in IEC 62386-206, covers DC signal converters [11]. These are the bridge between DALI and analogue-controlled equipment. Their features include:
- a choice of logarithmic or linear dimming characteristic [11]
- a selectable output range of 0-10 V or 1-10 V [11]
- an adjustable physical minimum level [11]
For contractors, DT5 converters are a practical way to bring analogue drivers or third-party equipment under DALI control. Choosing the right output range and dimming curve during commissioning is essential. A mismatch can cause poor low-end dimming or lamps that never fully switch off.
DT6: LED Drivers (Part 207)
DT6 is the workhorse of modern DALI installations. IEC 62386-207:2018 covers control gear for LED modules (device type 6). It applies to electronic lighting equipment in line with IEC 61347, with DC supplies added [7].
Edition 2.0 of Part 207, the DALI-2 version for LED drivers, was published on 12 April 2018. It replaced the first edition from 2009 [8]. If you are specifying new equipment, check which edition the driver is certified against.
Functionally, a DT6 LED driver uses one short address to control one output, such as the light level of a set of connected LEDs [4]. That one-address, one-output model is simple and predictable, but it has consequences for addressing.
DT8: Colour Control (Part 209)
DT8 is defined in IEC 62386 Part 209, which covers control gear for colour control [5]. Where DT6 controls a single light level, DT8 adds commands that let a controller adjust the colour of the light output. DT8 is therefore relevant wherever the specification calls for colour-adjustable lighting. When commissioning these systems, make sure your controller and your drivers support the same colour control features. Otherwise scenes may not reproduce as intended.
Why Device Type Affects Your Address Budget
Addressing is one of the most practical reasons to understand device types. A single DALI network supports at most 64 short addresses for control gear [13]. Every short address counts.
The catch is multi-channel hardware. A dual-channel DT6 driver uses two short addresses, because DT6 control gear accepts only one setpoint per address [14]. A luminaire with a dual-channel DT6 driver therefore uses up your address budget faster than its physical count suggests. On larger projects, this can be the difference between one DALI line and two.
When planning a network, count short addresses, not drivers. Check whether multi-channel devices are DT6 or use another approach. Ask the luminaire manufacturer how many addresses each fitting will occupy before you finalise the line layout.
Practical Tips for Installers
- Check datasheets for the Part number. Use the minus-201 rule to convert it to a DT number [1].
- Query device types during commissioning. QUERY DEVICE TYPE confirms what is actually installed [3]. This helps catch substitutions before handover.
- Expect multiple DT responses. A device that implements several Parts can report more than one type [3].
- Plan addresses carefully. Keep the 64 short address limit in mind [13], and account for multi-channel DT6 drivers [14].
- Configure DT5 converters deliberately. Set the output range and dimming curve to suit the connected equipment [11].
Conclusion
DALI device types give a clear structure to a varied range of control gear. Fluorescent ballasts, HID gear, incandescent controllers, DC signal converters, LED drivers and colour control gear each have their own Part of IEC 62386, their own DT number and their own command set. Knowing which type you are dealing with helps you specify the right equipment, plan your address budget and commission systems that behave as the client expects.
FAQ
How do I work out a device type from an IEC 62386 Part number? Subtract 201 from the Part number. For example, Part 207 is DT6 and Part 209 is DT8 [1].
Do DALI sensors and push-button interfaces have device type numbers? No. DT numbers only exist for control gear Parts. Input devices and application controllers have none [2].
Can one driver report more than one device type? Yes. A device can implement several Parts, so it can report more than one DT number in reply to QUERY DEVICE TYPE [3].
Why does my dual-channel LED driver use two addresses? DT6 control gear accepts only one setpoint per short address, so a dual-channel DT6 driver needs two short addresses [14].
What is DT5 used for? DT5 covers DC signal converters. They offer selectable logarithmic or linear dimming, a 0-10 V or 1-10 V output range, and an adjustable physical minimum level [11].