Emergency Lighting and DALI: An Overview of Standards and Test Requirements

Lumcue Team7 min read

Emergency lighting is a life-safety system. It is also one of the areas where DALI can make routine testing and record-keeping more manageable. For installers and electrical contractors, the challenge is understanding how the standards fit together. These include the DALI standard for emergency control gear, the certification rules behind DALI-2 products, and the UK standards that govern design, inspection and documentation.

This article gives a practical overview of those standards and the test requirements they bring. It is a starting point, not a substitute for the standards themselves. Anyone designing, installing or certifying emergency lighting should work from the current published documents.

Where DALI Fits Into Emergency Lighting

DALI, the Digital Addressable Lighting Interface, is defined in the multi-part international standard IEC 62386 [4]. Different parts of the standard cover different types of device. The part that matters most for emergency lighting is IEC 62386-202 [1].

IEC 62386-202 and Device Type 1

IEC 62386-202 sets out the particular requirements for control gear used in self-contained emergency lighting. DALI refers to this category as device type 1 [1]. The full title is "Digital addressable lighting interface - Part 202: Particular requirements for control gear - Self-contained emergency lighting (device type 1)" [1].

Its scope covers control gear for the digital control of electronic lighting equipment associated with self-contained emergency lighting, as described in IEC 61347-2-7 [2]. In practical terms, it covers emergency luminaires or emergency modules that contain their own battery and that can be addressed, queried and instructed over a DALI line.

This matters on site. When you commission an emergency luminaire on a DALI system, you are not just dealing with a dimmable light source. Device type 1 gear carries its own set of emergency-specific features, and these are defined in this part of the standard [1].

The 2022 Second Edition

IEC 62386-202 was revised. The 2022 second edition cancels and replaces the first edition published in 2009, and IEC describes it as a technical revision [3]. The DALI Alliance announced the publication of Edition 2.0 of Part 202 [4] and confirmed that it replaces the 2009 first edition [8].

For contractors, the main takeaway is that emergency gear and documentation on a project may refer to different editions of Part 202 [3]. This is especially likely on refurbishments or extensions where older equipment remains in place. Checking which edition a product was designed against can help avoid confusion during commissioning.

DALI-2 Certification and Emergency Products

Many installers specify DALI-2 certified products for interoperability. It is worth understanding how DALI-2 certification relates to the IEC standard.

DALI-2 Is Based on IEC 62386, With Small Differences

The DALI Alliance states that DALI-2 certification is based on the IEC 62386 standard, but that there are some small differences [5]. A product that claims compliance with an IEC part is therefore not automatically the same as a DALI-2 certified product.

Which Edition Applies?

The publication of a new IEC edition does not automatically change what certified products must follow. Members of the DALI Alliance working towards product certification should keep using the edition or amendment of each IEC 62386 part listed in the Alliance's "Allowed Parts of IEC 62386" document [6].

Alongside this, the DALI Alliance publishes "Clarifications and Recommendations for IEC 62386", an additional set of requirements that are necessary for DALI-2 certification [7].

For installers, these are mainly manufacturer-facing documents. They still help explain something you may see in the field. Two emergency products may both refer to the same IEC part [1], yet behave slightly differently depending on certification status and the edition they were built to. When you troubleshoot a mixed installation, it helps to check each product's certification and documentation.

UK Standards for Emergency Lighting

DALI governs how emergency gear communicates. It does not replace the national standards that cover emergency lighting design, inspection and record-keeping. In the UK, several documents work together.

BS 5266 and Its Related Standards

BS 5266 is the core UK code of practice for emergency lighting. It has many references to other standards, including BS EN 1838, BS EN 50172 and BS 7671 [13]. The IET notes that a designer would need access to these standards [13]. In practice, compliance with emergency lighting requirements is rarely a matter of reading one document in isolation.

BS EN 50172: Inspection, Testing and Certificates

BS EN 50172 is particularly relevant to testing and documentation. Clause 6.2 states that on completion of a yearly inspection and test schedule, as required in the periodic inspection, a test certificate should be supplied to the person responsible for the premises [11].

The Emergency Lighting Logbook

Record-keeping is just as important as the tests themselves. According to the IET, the format of the emergency lighting logbook should be in line with BS EN 50172, Clause 6.3 Log book (Reporting) [12]. A well-kept logbook gives the responsible person, and anyone inspecting the premises, a clear history of tests, faults and remedial work.

Function Tests and Duration Tests in DALI Systems

Emergency lighting testing is generally discussed in terms of two test types: function tests and duration tests [10][14]. The required frequency, duration and acceptance criteria are set out in the applicable standards. Installers should take these details from BS 5266, BS EN 50172 and the manufacturer's documentation rather than from general guidance.

DALI-based systems can make these tests easier to start, schedule and record. Products in the market show the range of approaches.

Local Test Initiation

Some devices allow tests to be started directly at the hardware. For example, function tests and duration tests can be started via a button on the Lunatone DALI-2 EM Guard [10]. The same device includes an integrated 220 mA DALI bus power supply, suitable for powering a DALI line with up to 64 standard DALI devices [9]. That is useful on smaller installations where a separate bus power supply would otherwise be needed.

Scheduled and Remote Testing

Other systems focus on central control. Helvar, for instance, lets users schedule automated tests for later, or start a function or duration test on demand from their workdesk [14]. This kind of approach can reduce the need for site visits to start routine tests. Results still need to be reviewed, acted on and recorded in line with the logbook requirements [12].

Practical Points for Installers

Whatever system you use, a few principles apply:

  • Confirm device types. Make sure emergency gear is identified as device type 1 [1] so it is handled correctly during commissioning.
  • Check certification and editions. Note whether products are DALI-2 certified and which edition of Part 202 they follow [3][6].
  • Plan bus power. If a device provides bus power, account for its rated capacity when designing the line [9].
  • Keep the paperwork in order. Make sure the logbook format follows BS EN 50172 [12], and that a test certificate is supplied after the yearly inspection and test [11].

A Note on Lumcue and Emergency Lighting

Lumcue is DALI commissioning software. It does not currently support emergency lighting. For emergency testing, monitoring and reporting, use the tools and documentation provided by your emergency lighting equipment manufacturer or system supplier, and follow the relevant standards.

FAQ

What is DALI device type 1? Device type 1 is the DALI designation for self-contained emergency lighting control gear. Its particular requirements are defined in IEC 62386-202 [1].

Has IEC 62386-202 been updated? Yes. The 2022 second edition replaces the 2009 first edition and is a technical revision [3][8].

Is a DALI-2 certified product the same as one that meets IEC 62386? Not exactly. DALI-2 certification is based on IEC 62386, but there are some small differences [5]. It also requires compliance with the DALI Alliance's additional clarifications and recommendations [7].

Which standard covers emergency lighting logbooks? The logbook format should be in line with BS EN 50172, Clause 6.3 [12].

Does Lumcue support emergency lighting? No. Lumcue does not currently support emergency lighting. Use manufacturer-supplied tools for emergency testing and reporting.