DALI Commissioning Checklist: From First Power-On to Handover

Lumcue Team8 min read

DALI commissioning is not plug-and-play. Because all configuration lives inside the devices on the bus, a systematic approach prevents the most common failures: missed addresses, wrong group assignments, and scenes that fire for the wrong zone.

"When commissioning this is very complex because the luminaires must first be identified and then configured." [2]

This checklist covers the commissioning sequence from initial power-on through project file handover.

Before You Start

Gather from the design pack:

  • Final address-to-luminaire mapping (typically a numbered plan or spreadsheet)
  • Group zone plan (which luminaires belong to which zones)
  • Scene schedule (what brightness level each group shows for each scene)
  • Fade time requirements (default and per-zone if specified)

Check the installation:

  • Bus power supply installed and correctly rated for the line
  • All DALI wiring terminated; cable length within 300 m [1]
  • All luminaire drivers powered and DALI terminals connected

A DALI line can support up to 64 control gear and, in DALI-2, an additional 64 control devices.

"In DALI-2, each DALI subnet can have 64 control gear and 64 control devices." [1]

"Each DALI-2 system requires a bus power supply, which can be a standalone device or integrated with another device." [1]


Step 1 — Bus Scan

With the commissioning software connected, perform a bus scan. The software discovers all devices that respond to broadcast commands.

Check:

  • Device count matches the drawing (if the count is lower, a device is unpowered, miswired, or has a defective DALI terminal)
  • No "duplicate address" warnings (fresh devices from the factory typically have no short address assigned; if a device was previously used, it may retain an old address)
  • Bus voltage is within the 12 V – 22.5 V window [5]

If devices are missing from the scan, power-cycle individual luminaires or measure bus voltage at the last detected device to locate the break.


Step 2 — Automatic Address Assignment

The commissioning software assigns short addresses to all discovered devices. Most tools do this automatically by broadcasting a randomise command, then narrowing down to each device one by one.

"configuration of a DALI line is performed by the Master via PC software" [2]

After address assignment, every device on the line has a unique short address (0–63). At this stage, addresses are arbitrary — a device at address 0 may be physically anywhere in the space.

Check:

  • All devices responded and received a short address
  • Total addressed count matches the bus scan result

Step 3 — Physical Identification

Map each short address to its physical location. Most commissioning tools let you send a test command (identify flash or set to full output for 2 seconds) to a single address while a colleague marks the plan.

Walk the space methodically — row by row, zone by zone. Update the address-to-luminaire drawing in real time. This step is time-consuming but essential: without a correct physical map, group assignment and scene programming in later steps will produce the wrong result.


Step 4 — Group Assignment

Assign each device to one or more groups based on the zone plan.

"the group allocation and the light scene values are stored in the control gear." [2]

DALI stores group memberships inside each device's non-volatile memory, not only in the controller software. This means:

  • A device can belong to multiple groups simultaneously (up to 16 groups per device, groups 0–15) [5]
  • Group assignments survive a controller replacement
  • Replacing a failed driver resets its group memberships to factory default; the project file is needed to restore them

Check:

  • Each device has the correct group assignments per the zone plan
  • Test each group by sending a dim command: only the expected luminaires should respond
  • Luminaires that should span multiple zones (e.g., a corridor that belongs to both Zone A and Zone B) are in both groups

Step 5 — Scene Programming

For each scene number in the schedule, set the target brightness level in each relevant device.

"the group allocation and the light scene values are stored in the control gear." [2]

Scene values (0–254, plus MASK = 255) are stored in each device. A device with MASK set for a given scene number ignores that scene recall command.

For each scene:

  1. Set all devices in scope to their target level
  2. Confirm visually that the output matches the brief
  3. Store the scene number in all devices

Common scenes to verify:

  • Full occupancy (maximum task light)
  • Presentation or AV mode (dimmed ceiling, raised display zone)
  • Cleaning (full output all zones)
  • After-hours or safe off (minimum emergency-compatible output or off)
  • Emergency hold (if applicable — check emergency fitting requirements separately)

Step 6 — Fade Time and Minimum/Maximum Level

Check default fade time, minimum light level, and maximum light level for each device or group. The defaults from factory are often not appropriate for the installation:

  • Fade time: default is typically 0.7 s; building briefs often specify 1–3 s for smooth transitions
  • Minimum level: set above the driver's instability threshold (consult data sheet for the exact value)
  • Maximum level: usually full output, but may be limited for glare control in specific zones

"DALI is a bidirectional protocol which makes for easier commissioning and greater flexibility in control gear." [3]

The bidirectional protocol means each device can report its current settings back to the software for verification — useful for confirming that a write succeeded across all devices in a group.


Step 7 — Input Device Commissioning (DALI-2)

If the installation uses DALI-2 input devices (push buttons, occupancy sensors, light sensors), commission them after the control gear is confirmed.

"Input devices are multi-master. They can be polled, but are normally used in event-driven mode." [1]

"Examples include push-buttons, sliders, occupancy sensors, and light sensors." [1]

For each input device:

  1. Confirm it appears in a bus scan with its own address (in the separate control-device address space, 0–63)
  2. Set the instance type (push button: Type 1; occupancy sensor: Type 3; light sensor: Type 4)
  3. Configure binding: which group or individual address does this input device command?
  4. Test: press the button or trigger the sensor; confirm the expected group responds correctly

Step 8 — Fault Reporting Check

DALI drivers report lamp failure and driver failure back to the controller over the bus. Verify the fault monitoring is active.

"Faulty control gears can be replaced easily by new ones." [2]

Send a test fault query to a sample of devices. The controller should log the response. Confirm fault alerts are configured to reach building management, the facilities team, or the maintenance contractor.

Note on replacement: When a driver fails and is replaced, the new device arrives with factory defaults. All settings — short address, group memberships, scene values, and fade times — must be re-written from the project file.

DALI uses a two-wire bus; polarity-independent installation means a replacement device has no risk of miswiring at the DALI terminals.

"DALI uses a two-wire bus that connects up to 64 devices per line without polarity constraints" [4]


Step 9 — Final Walkthrough

Before signing off:

  • Trigger each scene from every control point (push button, wall panel, BMS command) and confirm the correct response
  • Dim each group through the full range; verify smooth transitions and no drop-out at the minimum level
  • Confirm emergency fittings respond to emergency test commands (typically a separate process per IEC 62386-202)
  • Walk the space in the dark and confirm no unexpected light leakage from devices that should be off

Step 10 — Handover Pack

The handover pack must include:

  1. Commissioning project file — the saved software database, including all addresses, groups, scenes, and fade times
  2. Address-to-luminaire drawing — marked-up plan showing each device's short address and group memberships
  3. Scene schedule — what each scene number means in each zone, and the target levels
  4. Input device map — for DALI-2 installations, which input device addresses are bound to which groups
  5. Bus power supply data sheet and location — for future maintenance
  6. Replacement procedure — brief note explaining that a replacement driver needs re-commissioning from the project file

Without the project file, a failed driver requires the commissioning engineer to return and re-learn the zone plan from scratch. Treat the project file as a critical asset and ensure it is stored in at least two locations — client's BMS documentation and a remote backup.

FAQ

How long does commissioning take for a typical office floor? Time depends on device count and access constraints. Expect 1–2 hours for address scanning and identification on a 64-device line, plus 1–2 hours for group assignment, scene programming, and testing. A full floor with multiple DALI lines and DALI-2 input devices may take a full day.

What tools are needed for DALI commissioning? A DALI commissioning interface (USB-to-DALI adapter or controller with built-in commissioning port) and compatible software. Most manufacturers supply their own commissioning tools; third-party tools that support IEC 62386 are also available.

Can DALI be commissioned without a PC? Some DALI controllers include a basic auto-addressing function that assigns random addresses without a PC. However, group assignment, scene programming, and the physical address map all require software. Auto-addressing alone does not produce a commissioned installation.

What happens to the DALI configuration if the controller is replaced? Group memberships, scene values, and fade times are stored in each device. The controller replacement does not erase device configuration. However, the software project file is needed to verify and adjust settings after the replacement. A new controller must re-learn or import the address map.