DALI Bus Power Supply Sizing: Voltage, Current, and Cable Rules
DALI carries power and data on the same two-wire bus. Before a single commissioning command can be sent, the bus needs a stable power supply sized for the devices it will serve. Undersizing the supply or running cable past the electrical limits causes intermittent command failures that are slow to diagnose.
The Bus Electrical Limits
The DALI specification defines a narrow operating window for bus voltage and current.
"DALI bus voltage: 12V-22.5V (typical 16V)" [2]
"DALI system current: <250mA" [2]
The DALI Alliance systems page states the same figures from the standard:
"Bus power supplies provide typically 16 V and up to 250 mA to provide power to devices connected to the bus." [1]
The 250 mA limit applies to the entire line, not to individual devices. Each DALI driver draws a small quiescent current from the bus; add up the totals across all devices and keep the sum below 250 mA. Consult manufacturer data sheets for exact per-device figures. DALI-2 input devices (sensors, push buttons) also draw bus current, so a mixed line needs to account for both device populations.
DALI power and data share the same pair of wires, which simplifies cabling.
"The DALI bus carries DALI power and data on the same pair of wires." [1]
Cable Length and Cross-Section
The maximum permitted cable run is 300 m measured between the two furthest-apart devices on the line — not 300 m from the power supply.
"The maximum cabling length (the distance between the furthest-apart devices) is 300m." [1]
"cable length of up to 300m (1.5mm2 wire cross section)" [2]
The DALI Alliance systems page specifies the reference cable cross-section:
"typically using standard 2-core cable (1.5 mm²)." [1]
Using a smaller cable cross-section increases loop resistance and reduces the effective voltage at the far end of the bus. If you deviate from the reference conductor size, calculate the voltage drop and verify that the furthest device still receives adequate bus voltage under full load.
Wiring Topology
Unlike RS-485 or KNX, DALI does not require a strict daisy-chain or star topology. Any free wiring layout — star, ring, branch — is permitted.
"The polarity of the wires does not have to be observed, and free wiring topology is allowed." [1]
Helvar confirms the polarity-independence:
"DALI uses a two-wire bus that connects up to 64 devices per line without polarity constraints" [3]
In practice this means DALI cable can follow conduit runs designed for power wiring without re-routing for bus topology. T-junctions and ring loops are acceptable. The only limit is the total cable length and the 250 mA current budget.
Choosing a Bus Power Supply
The DALI standard requires every line to have a dedicated bus power supply — it cannot be shared across multiple DALI lines.
"Each DALI-2 system requires a bus power supply, which can be a standalone device or integrated with another device." [1]
"Integrated with another device" typically means the DALI controller or gateway contains a built-in bus power supply for one line. Standalone supplies are used when the controller is rack-mounted in a panel away from the bus devices.
Standalone vs Integrated
Standalone supplies are installed in the DB or mounted near the first luminaire on the run. They provide clean, isolated power and are the simplest option when the controller does not include a built-in supply.
Integrated supplies (typically one per controller output) are built into most DALI controllers and gateways. Check the data sheet: some controllers supply only enough current for a lightly loaded line, which may be insufficient for a full 64-device circuit including input devices.
Sizing Calculation
- Count the number of control gear (drivers) on the line.
- Count the number of DALI-2 input devices (sensors, push buttons).
- Sum the bus current draw for each device type from manufacturer data sheets.
- Add a headroom margin.
- Choose a supply rated at or above that figure, up to the 250 mA line maximum.
Worked example: 30 drivers at 2 mA each = 30 × 2 = 60 mA; 10 input devices at 6 mA each = 10 × 6 = 60 mA; total = 60 + 60 = 120 mA. A supply rated at or above 120 mA covers this line; select the next standard rating above 120 mA for headroom.
One Supply Per Line
DALI addresses are line-scoped: address 0 on Line 1 and address 0 on Line 2 are different devices. A controller that manages multiple DALI lines typically has one bus power supply output per line, or relies on standalone supplies for each. Never share a single bus power supply across two DALI lines — the address spaces would overlap and commissioning commands would reach the wrong devices.
"Maximum 64 clients per controller" [4]
"DALI is a bidirectional protocol which makes for easier commissioning and greater flexibility in control gear." [4]
The bidirectional nature means the controller can query individual device status in addition to sending commands — but only if the bus power supply is stable. A marginal supply causes devices to reset or fail to respond, producing diagnostics that appear device-level but are actually supply-level.
FAQ
Can the DALI bus power supply be shared with the mains luminaire supply? No. The DALI bus is a SELV (Safety Extra Low Voltage) circuit isolated from mains. A dedicated transformer or power supply provides the low-voltage DC bus rail, separate from the mains supply to the luminaire drivers.
What happens if the bus power supply is undersized? Devices near the end of the run see reduced bus voltage. They may respond intermittently, refuse to commission, or reset unexpectedly. The failure looks device-level in commissioning software but is actually a supply or cable problem.
Can DALI bus cable run in the same conduit as mains wiring? This depends on local wiring regulations. The DALI bus voltage (16 V SELV) is inherently safe, but proximity to mains can induce interference. Where permitted, use screened cable or maintain physical separation between DALI and mains conductors.
Is there a minimum cable cross-section for DALI? The standard references 1.5 mm² as the reference conductor. Smaller cross-sections reduce the effective cable length before voltage drop becomes a problem. If a smaller cross-section is used on shorter runs, verify the bus voltage at the furthest device remains within the permitted window.