DALI Addressing Explained: Short, Group, Broadcast and Scene Addresses

Lumcue Team5 min read

DALI — Digital Addressable Lighting Interface — is defined by the international standard IEC 62386 and uses a two-wire low-voltage bus to let a controller communicate individually with every luminaire driver, sensor, and switch on a lighting circuit.

"DALI is an industry-standardized protocol, and is specified in the multi-part international standard IEC 62386." [1]

Understanding its four addressing modes is the starting point for every DALI design and commissioning task.

The Four Addressing Modes

1. Short Address (Individual Device)

Every control gear (LED driver, fluorescent ballast, emergency unit) on a DALI line receives a unique short address during commissioning. The standard allows up to 64 addressable devices per line.

"up to 64 addressable DALI operating devices" [3]

Short addresses let a controller send a command to one specific device — for example, to query its fault state, adjust its minimum light level, or read back its current output.

"each DALI device can be assigned a separate address, allowing digital control of individual devices" [1]

Short addresses are stored in non-volatile memory inside the device and survive power cycles. The addressing is typically done automatically by commissioning software, which randomises addresses and then narrows down to each device by switching them one at a time.

2. Group Address

After short addresses are assigned, the commissioning engineer organises devices into groups. Each device can belong to up to 16 groups simultaneously (groups 0 to 15).

"Each operating device can be assigned to one or more of 16 groups, which greatly increases flexibility" [3]

A group command reaches all devices in that group simultaneously. All downlights in an open-plan zone, for instance, can be dimmed with a single command to Group 4. Group memberships are stored in each device, not only in the controller — so the configuration survives a controller replacement.

"the group allocation and the light scene values are stored in the control gear." [5]

3. Broadcast

A broadcast command has no address. Every device on the line responds — useful for end-of-day all-off, emergency shutdown, or resetting a line during fault-finding.

Broadcast overrides whatever state any individual device or group is in. Use it deliberately: in occupied spaces it will cancel any active scene or dim level without zone distinction.

4. Scene Recall

Scenes are pre-programmed brightness levels stored inside each device. Each device holds up to 16 stored brightness levels, one per scene number (0 to 15).

"In each DALI operating device up to 16 different light values can be saved as scene value." [3]

A scene-recall command tells every addressed device (individual, group, or broadcast) to move to its stored level for that scene number. A device that should not respond to a particular scene has its slot set to MASK (value 255), causing it to ignore the scene call.

Typical office scene assignments: Scene 0 for full occupancy, Scene 1 for presentation mode (dim rear, raise front), Scene 4 for cleaning, Scene 15 for a safe-off state. Scene numbers are arbitrary — meaningful labels exist only in the commissioning software.

DALI-2: A Second Address Space for Input Devices

Original DALI addressed only control gear (drivers). DALI-2 extends the protocol to input devices — sensors and push buttons — and assigns them their own separate address space.

"In DALI-2, each DALI subnet can have 64 control gear and 64 control devices." [2]

This means a DALI-2 line can carry 64 drivers and 64 sensors or switches at the same time without address collisions. The two address spaces are kept separate by the command structure.

DALI uses a two-wire bus and is polarity-independent — there is no required orientation for the two conductors.

"DALI uses a two-wire bus that connects up to 64 devices per line without polarity constraints" [4]

Addressing Summary

Mode Count Stored in Typical use
Short address Up to 64 (control gear) Device non-volatile memory Individual device commands, diagnostics
Group address 16 (0–15) Device non-volatile memory Zone dimming, scene delivery to groups
Broadcast 1 N/A All-off, line reset
Scene 16 (0–15) Device non-volatile memory Pre-set brightness levels per activity

Practical Tips

Record the address map on as-built drawings. Address 0 in the software is meaningless without a physical location record. During commissioning, print or export the address-to-luminaire map and include it in the handover pack.

Plan group zones before commissioning. Group assignments are easy to change in software but slow to update in an occupied building. Agree the zone strategy before the commissioning engineer arrives.

Use MASK (255) for scene slots deliberately. If a luminaire should not react to a particular scene, set its slot to MASK rather than leaving it at the default. This avoids unexpected behaviour when scenes fire.

Keep the commissioning project file. Group memberships, scene values, and fade times are stored inside each device. Without the project file, replacing a failed device requires manual re-commissioning of all settings.

FAQ

What is the maximum number of DALI devices on one line? Up to 64 control gear (drivers, ballasts, emergency units) per line. DALI-2 adds a parallel address space of up to 64 control devices (sensors, push buttons), so a DALI-2 line can hold up to 128 individually addressable objects.

Can one DALI device belong to more than one group? Yes. Each device stores a bitmask with one bit per group (0–15). It responds to any group whose bit is set. This allows overlapping zones — a luminaire can belong to both Group 3 (office east) and Group 8 (whole floor) at the same time.

What happens to scenes and groups if a driver is replaced? The replacement driver arrives with factory defaults. All stored settings — short address, group memberships, scene values, and fade times — must be re-written from the commissioning project file.

Is DALI polarity-sensitive? No. The two bus conductors can be swapped without affecting operation. This simplifies installation and avoids wiring errors.