DALI vs DALI-2: What Changed and Why It Matters for New Installations
Most lighting professionals refer to DALI as a single standard. In practice there are two generations with significant differences in how compliance is verified, which device types are standardised, and what interoperability you can rely on.
The Core Difference: Self-Declaration vs. Independent Certification
Under original DALI (DALI version-1), manufacturers assessed their own products against the standard.
"DALI version-1 product compliance is based solely on self-declaration" [2]
"compliance was based on self-certification and/or declaration by individual DALI device manufacturers." [5]
This meant the DALI logo on a product carried no independent verification. In practice, subtle implementation differences across manufacturers could produce visible discrepancies — different dimming curves, inconsistent fade behaviour — on multi-brand projects.
"full interoperability for DALI version-1 devices was never guaranteed" [5]
DALI-2 replaces self-declaration with mandatory independent certification run by the DALI Alliance (DiiA).
"DALI-2 certification involves independent verification of test results." [2]
"DALI-2 test results are independently verified by the DALI Alliance before certification is granted." [1]
"DALI-2 also includes much more comprehensive testing than DALI version-1" [1]
Only products that pass this process may carry the DALI-2 mark.
"Only certified products can carry the DALI-2 trademarks (wordmark or DALI-2 logo)" [2]
"Only DALI devices that have been independently validated and certified to meet the DALI-2 standard can carry the DALI-2 logo" [5]
Helvar describes the same restriction: the DALI-2 logo "can only be used on products tested and certified by the DALI Alliance." [3]
To verify a product's certification status, check the DALI Alliance public product database at dali-alliance.org.
Change 2 — Input Devices Added to the Standard
Original DALI defined only control gear: LED drivers, fluorescent ballasts, emergency fittings. Sensors and switches were not part of the standard.
"One of the most significant changes was the addition of control devices (including application controllers and input devices)" [1]
"which were not included at all in the original version of the standard" [1]
"Moreover, control devices were not part of DALI version 1." [5]
DALI-2 adds a complete specification for control devices under IEC 62386 Part 103, with specific device-type parts for push buttons (301), analogue inputs (302), occupancy sensors (303), and light sensors (304).
"A separate standard for control devices (Part 103)" was defined under Edition 2. [4]
Because input devices are now standardised at the protocol level, a DALI-2 push button from one manufacturer can directly drive lighting scenes on a DALI-2 driver from another manufacturer — without proprietary gateways or parallel wiring.
Expanded Address Space
DALI-2 also gives input devices their own address space, separate from control gear.
"With DALI-2 up to 64 operating devices and 64 control devices on one DALI line are possible!" [4]
"A single DALI network can support at most 64 short addresses for control gear." [5]
This means a fully populated DALI-2 line can carry 64 drivers plus 64 sensors/buttons simultaneously without address conflicts.
Change 3 — When Was DALI-2 Released?
"Since November 2014, a new version of the DALI standard is available, the Edition 2 also called DALI-2." [4]
The certification programme built around Edition 2 is what the industry now calls DALI-2. Products certified to the earlier edition are sometimes referred to as "DALI registered" — a programme that is now closed to new entries.
Backward Compatibility
DALI-2 products are backward-compatible with original DALI systems at the physical and command level.
"Basically, the same commands are used for DALI and DALI-2, so DALI-2 devices can be easily used in conventional DALI systems." [4]
A DALI-2 controller will manage older DALI drivers normally. The DALI-2-specific features — input-device binding, extended fading, advanced diagnostics — are simply unavailable for older devices.
What This Means for New Projects
Specify DALI-2 certified products. Certification is the only way to ensure genuine multi-vendor interoperability. A product without DALI-2 certification has no independent verification of its compliance.
Choose IEC 62386-3xx input devices. These communicate natively on the DALI bus, eliminating the need for separate switch wiring. A DALI-2 push button module and occupancy sensor each use one of the 64 input-device addresses on the line.
Plan for the certification database. The DALI Alliance's product database at dali-alliance.org is the authoritative source for confirming which products are certified. Verify before specification, not after delivery.
FAQ
Are DALI-2 products backward compatible with original DALI controllers? Yes, at the physical layer. DALI-2 control gear follows the same bus electrical specification, so an older controller can dim and switch DALI-2 drivers. Features unique to DALI-2 — input-device binding, multi-master timing, extended fade times — are simply unused.
Can original DALI sensors and switches work with DALI-2? Sensors and switches from the original DALI era communicated over separate dry-contact or analogue inputs — they were not bus devices. DALI-2 input devices (IEC 62386-3xx) are a new, bus-native product category.
How do I confirm a product is DALI-2 certified? Check the product against the DALI Alliance certification database at dali-alliance.org. A product claiming DALI-2 compliance without appearing in that database has not completed certification.
Does DALI-2 change the wiring? No. The physical layer — two-wire bus, polarity-independent, 16 V DC nominal, 250 mA maximum line current — is identical to original DALI. [6] Existing DALI cabling can be reused.